2 Installation
2.9 Connecting local inputs/outputs
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 47
2.9.2 Connecting outputs
A maximum current of 0.5 A is permissible per output. The outputs are short-
circuit proof to 24 VDC and GND.
If a short-circuit or overload occurs at one of the digital outputs, the output
will be switched off. Once the short-circuit or overload condition is fixed, the
output will automatically switch back on.
An LED is assigned to each output. A switched (active) output will be indi-
cated by the LED showing a green light.
Connect the outputs, unshielded, with a connection cable with a maximum
length of 30 m.
Figure 34: Connecting the local outputs of an XC-303-…PLC
Designation
Number of outputs Current/output[kb}
[mA]
Max. total current
[A]
XC-303-C32-002
4 500 2
XC-303-C21-001
XC-303-C11-000
XC-204-C20-002
XC-204-C21-001
XC-204-C11-003 2 500 1
XC-204-C10-000 2 500 1
XC-104-C10-000
PE
24 V
0 V
X1
Q1
Q2
Q3
Q4
_
X2
U
L
R
L