EasyManua.ls Logo

Eaton XC-303 Series - Power Supply for Local Inputs;Outputs on XC-204

Eaton XC-303 Series
193 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 Appendix
20.3 Technical specifications
176 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
20.3.3 Power supply for local inputs/outputs on XC-204-…, XC-303-…
On XC-204-… devices, the local inputs and outputs are powered through the
system power supply. On XC-303-… devices, the local inputs and outputs
are powered through terminal
X2/UL; this terminal is powered externally.
Power supply of local inputs/outputs XC-204-… XC-303-
Rated operating voltage U
L
System supply X2/U
L
Rated value U
e
24 V DC 24 V DC
admissible range 19.2 - 30V DC 18 - 30V DC
Residual ripple
5% 5%
Protection against polarity reversal
Yes
Input current I
L
max. 1 A max. 2 A
Galvanic separation U
L
to
System bus no Yes
POW no Yes
RS485 no Yes
CAN1
no Yes
CAN2 Yes
Local inputs no no
Local outputs no no
ETH0…ETH2 Yes Yes
Flag Display none LED, single-colored, green

Table of Contents

Related product manuals