20 Appendix
20.3 Technical specifications
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 177
20.3.4 Local inputs XC-204-…, XC-303-…
Each of the transistor inputs can alternatively also be configured as an out-
put.
Digital inputs (EN 61131-2, type 1) XC-204-… XC-303-…
Inputs (quantity) 2 4
Input rated voltage 24V DC, observe polarity 24V DC, observe polarity
Voltage levels 19,2…30V DC 18…30V DC
Input current per channel at rated operating voltage at 24 V normally 2.5 mA normally 2.5 mA
Switching levels as per EN 61131-2
Limit values type “1” low < 5, high > 15 V DC low < 5, high > 15 V DC
Input delay
Off r On < 0.2ms < 0.2ms
On r Off < 0.2ms < 0.2ms
of which the following can be used as interrupt inputs: I1…I2 I1…I4
Galvanic separation from
From each other no no
Local outputs no no
System bus no Yes
POW no Yes
RS485 no Yes
CAN1 no Yes
CAN2 – Yes
ETH0…ETH2 Yes Yes
Flag Display
LED, single-colored, green LED, single-colored, green
Cable length (unscreened)
< 30m < 30m