20 Appendix
20.3 Technical specifications
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 177
20.3.4 Local inputs XC-204-…, XC-303-…
Each of the transistor inputs can alternatively also be configured as an out-
put.
Digital inputs (EN 61131-2, type 1) XC-204-… XC-303-
Inputs (quantity) 2 4
Input rated voltage 24V DC, observe polarity 24V DC, observe polarity
Voltage levels 19,2…30V DC 18…30V DC
Input current per channel at rated operating voltage at 24 V normally 2.5 mA normally 2.5 mA
Switching levels as per EN 61131-2
Limit values type “1” low < 5, high > 15 V DC low < 5, high > 15 V DC
Input delay
Off r On < 0.2ms < 0.2ms
On r Off < 0.2ms < 0.2ms
of which the following can be used as interrupt inputs: I1…I2 I1…I4
Galvanic separation from
From each other no no
Local outputs no no
System bus no Yes
POW no Yes
RS485 no Yes
CAN1 no Yes
CAN2 Yes
ETH0…ETH2 Yes Yes
Flag Display
LED, single-colored, green LED, single-colored, green
Cable length (unscreened)
< 30m < 30m