20 Appendix
20.3 Technical specifications
178 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
20.3.5 Local outputs XC-204-…, XC-303-…
Each of the transistor outputs can alternatively also be configured as an
input. If the PLC is RESET, the outputs will be switched off.
Digital outputs XC-204-… XC-303-
Channels (quantity) 2 4
Short-circuit proof Yes Yes
Isolation voltage 500 V AC
Heat dissipation per channel
Q1 to Q4 <0.1W <0.1W
Load circuits
Q1 to Q4 0.5 A 0.5 A
Output delay
Off r On typ. 0.1 ms typ 0.1 ms
On r Off typ. 0.1 ms
1)
typ 0.1 ms
1)
Duty factor 100% 100%
Simultaneity factor g 1 1
Galvanic separation from
From each other no no
from the inputs no no
System bus no Yes
POW no Yes
RS485 no Yes
CAN1 no Yes
CAN2
Yes
ETH0…ETH2
Yes Yes
Flag Display
LED, two-colored, green, red LED, single-colored, green
Cable length (unscreened) < 30m < 30m
1) without capacitive load