9 CAN
9.1 Configuring and commissioning CANopen
114 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
to
Figure 81: "Add device" dialog box for selecting CAN modules for the XN-312-GW-CAN
Select the XN300 slice module you want and then select <Add device>.
The XN300 slice module will be added to the "Devices" configuration struc-
ture.
A maximum of 32 XN300 slice modules can be added to the CANopen
device.
The device tree will now show all the devices.
Figure 82: XControl with CANopen master, CAN-Gateway XN-312-GW-CAN, and four
XN300 slice modules
If you are using analog modules, observe the following requirements:
If you use the default mapping (index 0x6401/x) for analog modules, you
will need to enable PDO-based transmission for these I/O slice modules
by setting the value of object index 0x6423, subindex 0 to TRUE.
Regulate the bus load on the CAN field bus
The following procedure is recommended in order to prevent the XN-
312-GW-CAN gateway from generating a heavy load on the CAN field
bus:
You can change the order of the XN300 slice modules in the
configuration structure by dragging and dropping them accord-
ingly.