1 Description of the Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-…
1.6 Functionality
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 27
Maximum cable length: 1200 m.
1.6.4.5 CAN
The CAN interfaces depend on the device model.
The CAN interfaces can be run individually as a CAN master or CAN device.
The CAN 1 interface (X4) on XC-303-…- devices is galvanically isolated from
power supply U
s
(X6). This is not the case for any other devices or CAN inter-
faces.
The CANopen protocol can be run simultaneously by the MFD-Titan.
Configuration: X4 and/or X5 plug connector, 3-pin, PLUG-FMC-3S spring-
loaded plug-in terminal block.
Table 5 Configuration of the CAN interface
Activating the bus termination resistors
Bus termination resistors must be installed at the first and last station on the
CAN bus. A bus termination resistor with a resistance of 120 can be acti-
vated with DIP switches for this purpose.
To activate the bus termination resistors for CAN 1, switch the following DIP
switch on S1 to the ON position:
XC-303-…: TC1
See also:
•Functionality Page 18
Technical data Page 172
XControl
CAN1 CAN2
XC-303-C32-002
1)
XC-303-C21-001
1)
XC-303-C11-000
XC-204-C20-002
XC-204-C21-001
XC-204-C11-003
XC-204-C10-000
XC-104-C10-000
1) electrically isolated
Plug connector X4, X5 CAN
1
CAN_H
2
CAN_L
3 GND CAN
1
2
3