3 Commissioning
3.9 Updating the operating system
70 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
For XC-104-… and XC-204-… devices:
"Bootloader"
"Linux"
"PLC Runtime System".
Click on the <Continue> button.
Stop the PLC
Switch the S1 Stop DIP switch to ON
Click on "Download" to start downloading the firmware.
Wait until the dialog box shows a message saying "Download success-
ful."
Then close the window with "RETURN."
Click on "close" to exit the Setup Wizard.
Start the PLC
Switch the S1 Stop DIP switch to OFF
Restart the Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-….
The update process when using removable media or a local directory
( Figure 48, page 69) is similar to that for FTP installation.
Procedure:
Insert the USB device or MicroSD memory card into the PC.
Select "Removeable Drive" in the "XC… OperatingSystem Download"
screen (a fig. 48).
Select the removable media directory and click on "Next."
Select the "XC303" device type and click on "Next."
Select the "PLC operating system" component and click on "Next."
Click on "Install" to start downloading the firmware.
Click on "Done" to exit the Setup Wizard.
The firmware files will be found in a directory on the removable medium
called XC…/Firmware.
If you want to use the device's USB port, make sure that you have acti-
vated it – please refer to Section “3.2 USB interface activation for
XC-104-… and XC-204-… devices”, page 53.