194 E300 Design Guide
Issue Number: 1
Parameter
Range(Ú) Default(Ö)
Type
Open-Loop RFC-A RFC-S Open-Loop RFC-A RFC-S
B01 Drive Control Mode Open-loop (1), RFC-A (2), RFC-S (3) RW Txt ND NC PT
B02 Motor Rated Current ±VM_RATED_CURRENT A Maximum Heavy Duty Rating RW Num RA US
B03 Motor Rated Voltage ±VM_AC_VOLTAGE_SET V
200V drive: 230 V
400V drive: 400 V
575V drive: 575 V
690V drive: 690 V
RW Num RA US
B04 Motor Rated Power Factor 0.000 to 1.000
0.850 RW Num RA US
B05
Open-Loop: Number Of
Motor Poles
Automatic (0) to
480 (240) Poles
Automatic (0)
Poles
RW Txt US
RFC-A: Number Of Motor
Poles
Automatic
(0) to 480
(240) Poles
Automatic (0)
Poles
RW Txt US
RFC-S: Number Of Motor
Poles
Automatic (0) to 480
(240) Poles
6 (3) Poles RW Txt US
B06 Motor Rated Frequency 0.0 to 550.0 Hz
50 Hz : 50Hz
60 Hz : 60 Hz
RW Num US
B07 Motor Rated Speed 0 to 33000 rpm 0.00 to 33000.00 rpm
50 Hz : 1500 rpm
60 Hz : 1800 rpm
50 Hz : 1450
rpm
60 Hz : 1750
rpm
3000.00
rpm
RW Num US
B09
Open-Loop: Open Loop
Control Mode
Ur S (0),
Ur (1),
Fixed (2),
Ur Auto (3),
Ur I (4),
Ur I (4) RW Txt US
RFC-S: Action On Enable
Disabled (0),
Short (1),
Short Once (2),
Long (3),
Long Once (4)
Disabled (0) RW Txt US
B10 Slip Compensation Enable Off (0) or On (1)
On (1) RW Bit US
B11 Motor Autotune
None (0)
Static (1)
Rotating (2)
None (0)
Static (1)
Rotating (2)
Inertia (3)
None (0) RW Num NC
B12
Low Frequency Voltage
Boost
0.0 to 25.0 %
3.0 % RW Num US
B13
Maximum Switching
Frequency
0 to VM_SWITCHING_FREQUENCY kHz 8 (4) kHz RW Txt RA US
B14
Minimum Switching
Frequency
0 to VM_MIN_SWITCHING_FREQUENCY kHz 3 (1) kHz RW Txt US
B15
Switching Frequency Step
Size
1 to 2 2 RW Num US
B16 Symmetrical Current Limit ±VM_MOTOR1_CURRENT_LIMIT % 165.0 %
175.0 %
RW Num RA US
B17
Percentage Over Current
Trip Level
10 (0), 20 (1), 30 (2),
40 (3), 50 (4), 60 (5),
70 (6), 80 (7), 90 (8),
100 (9) %
100 (9) % RW Txt US
B18 Motor Percentage Flux
0.0 to 150.0
%
RO Num ND NC PT
B19 Thermal Protection Mode 00 to 11 00 RW Bin US
B20
Motor Thermal Time
Constant 1
1.0 to 3000.0 s 89.0 s RW Num US
B21
Motor Protection
Accumulator Power-up
Value
Power down (0), Zero (1), Real time (2) Power down (0) RW Txt US
B22
Motor Thermal Time
Constant 2
1.0 to 3000.0 s 89.0 s RW Num US
B23
Motor Thermal Time
Constant 2 Scaling
0 to 100 % 0 % RW Num US
B24
Rated Iron Losses As
Percentage Of Losses
0 to 100 % 0 % RW Num US
B25
Motor Parameter Adaptive
Control
0 to 2 0 RW Num US
B26
Reverse Motor Phase
Sequence
Off (0) or On (1) Off (0) RW Bit US
B27 Fast Disable Off (0) or On (1)
RO Bit ND NC PT
B28 Enable High Speed Mode
Limit (-1), Disable (0),
Enable (1)
Disable (0) RW Txt US
B29
Motor Contactor Monitoring
Enable
Off (0) or On (1) Off (0) RW Bit US
B30
Motor Contactor Monitoring
Input
Off (0) or On (1) Off (0) RW Bit US
B31
Motor Contactor Control
Output
Off (0) or On (1)
Off (0) RO Bit ND NC PT

Table of Contents