Drive Control Mode (B01) is set to the current drive mode at power-up. The user can change the drive mode as follows:
1. Set Pr mm00 to 1253, 1254
2. Change
3. Drive Control Mode (B01) to the required mode
4. Initiate a drive reset
Provided Drive Active (L06) = 0 the drive will change to the new drive mode, and then load and save parameters to non-volatile memory. If Pr mm00
is not set to one of the specified values then the drive mode does not change on drive reset. The value in Pr mm00 determines which defaults are
loaded as follows.
Motor Rated Current (B02) is used as follows:
1. To define the rated operating conditions for motor thermal protection. See Motor Thermal Time Constant 1 (B20).
2. To define the range of the current limits.
3. In the motor control algorithm for Open-loop and RFC-A modes.
B01 Drive Control Mode
Mode Open-Loop, RFC-A, RFC-S
Minimum 1 Maximum 3
Default Units
Type 8 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE, ND, NC, PT
Value Text
1 Open-loop
2RFC-A
3RFC-S
Parameter mm00 Defaults loaded
1253 50Hz defaults to all menus
1254 60Hz defaults to all menus
B02 Motor Rated Current
Mode Open-Loop, RFC-A, RFC-S
Minimum −VM_RATED_CURRENT Maximum VM_RATED_CURRENT
Default Maximum Heavy Duty Rating (J05) Units A
Type 32 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW, VM, RA
B03 Motor Rated Voltage
Mode Open-Loop, RFC-A, RFC-S
Minimum −VM_AC_VOLTAGE_SET Maximum VM_AC_VOLTAGE_SET
Default See exceptions below Units V
Type 16 Bit User Save Update Rate 4 ms read
Display Format Standard Decimal Places 0
Coding RW, VM, RA
Voltage (V) Region Default Value (V)
200 All 230
400
50 Hz 400
60 Hz 400
575 All 575
690 All 690