278 E300 Design Guide
Issue Number: 1
If T5 T6 Analog Input 1 Invert (F40) = 0 then A
1I
= A
1S
otherwise A
1I
= -A
1S
A
1I
is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by Analog Input 1
Destination (F41).
See T5 T6 Analog Input 1 Scaling (F39).
See T5 T6 Analog Input 1 Scaling (F39).
See T5 T6 Analog Input 1 Scaling (F39).
See T5 T6 Analog Input 1 (F35).
See T5 T6 Analog Input 1 (F35).
F40 T5 T6 Analog Input 1 Invert
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
F41 Analog Input 1 Destination
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum AB99
Default A00 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Menu Param Alpha Numeric Decimal Places 3
Coding RW, DE, PT, BU
F42 T5 T6 Analog Input 1 Offset
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 2
Coding RW
F43 T5 T6 Analog Input 1 Minimum
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default -100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
F44 T5 T6 Analog Input 1 Maximum
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default 100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW