See T5 T6 Analog Input 1 Mode (F38).
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See T5 T6 Analog Input 1 Scaling (F39).
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See T5 T6 Analog Input 1 Scaling (F39).
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See T5 T6 Analog Input 1 Scaling (F39).
F45 T7 Analog Input 2 Mode
Mode Open-Loop, RFC-A, RFC-S
Minimum -4 Maximum 6
Default 6 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
-4 4-20 mA Low
-3 20-4 mA Low
-2 4-20 mA Hold
-1 20-4 mA Hold
0 0-20 mA
1 20-0 mA
24-20 mA Trip
3 20-4 mA Trip
4 4-20 mA
5 20-4 mA
6Volt
F46 T7 Analog Input 2 Scaling
Mode Open-Loop, RFC-A, RFC-S
Minimum 0.000 Maximum 10.000
Default 1.000 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW
F47 T7 Analog Input 2 Invert
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
F48 T7 Analog Input 2 Destination
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum AB99
Default G33 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Menu Param Alpha Numeric Decimal Places 3
Coding RW, DE, PT, BU