The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See T5 T6 Analog Input 1 Scaling (F39).
The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See T5 T6 Analog Input 1 Scaling (F39).
See T5 T6 Analog Input 1 (F35).
See T5 T6 Analog Input 1 (F35).
F55 T8 Analog Input 3 Destination
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum AB99
Default A00 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Menu Param Alpha Numeric Decimal Places 3
Coding RW, DE, PT, BU
F56 T8 Analog Input 3 Offset
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
F57 T8 Analog Input 3 Minimum
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default -100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
F58 T8 Analog Input 3 Maximum
Mode Open-Loop, RFC-A, RFC-S
Minimum -100.00 Maximum 100.00
Default 100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
F59 T8 Analog Input 3 Thermistor Type
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 9
Default 0 Units %
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
0 DIN44082
1KTY84
2 PT100 (4 W)
3 PT1000 (4 W)
4 PT2000 (4 W)
5 2.0mA (4 W)
6 PT100 (2 W)
7 PT1000 (2 W)
8 PT2000 (2 W)
9 2.0mA (2 W)