E300 Design Guide 321
Issue Number: 1
The timing diagram below shows the operation of the blocked elevator release feature:
This feature is not available in Open-Loop mode.
In status mode Parameter Displayed At Power-up (H39) defines which Menu 0 parameter is initially displayed at power-up.
Drive Name Characters 1-4 (H40) to Drive Name Characters 13-16 (H43) can be used to store a 16 character string which can be used to identify the
drive. The string is arranged as shown below.
This uses the standard ASCII character set.
See Drive Name Characters 1-4 (H40).
H39 Parameter Displayed At Power-up
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum A80
Default A06 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW, PT
H40 Drive Name Characters 1-4
Mode Open-Loop, RFC-A, RFC-S
Minimum -2147483648 Maximum 2147483647
Default 0 Units
Type 32 Bit User Save Update Rate N/A
Display Format String Decimal Places 0
Coding RW, PT
H41 Drive Name Characters 5-8
Mode Open-Loop, RFC-A, RFC-S
Minimum -2147483648 Maximum 2147483647
Default 0 Units
Type 32 Bit User Save Update Rate N/A
Display Format String Decimal Places 0
Coding RW, PT