322 E300 Design Guide
Issue Number: 1
See Drive Name Characters 1-4 (H40).
See Drive Name Characters 1-4 (H40).
The bits in Action On Trip Detection (H45) are defined as follows:
Bit 0: Stop on defined non-important trips
If bit 0 is set to one the drive will attempt to stop before tripping if any of the following trip conditions are detected: I/O Overload, An Input 1 Loss, An
Input 2 Loss.
Bit 1: Disable braking resistor overload detection
See Braking Resistor Rated Power (D15).
Bit 2: Disable phase loss stop
Normally the drive will stop when the input phase loss condition is detected. If this bit is set to 1 the drive will continue to run and will only trip when the
drive is brought to a stop by the user.
Bit 3: Disable braking resistor temperature monitoring
If hardware based braking resistor thermal monitoring is provided this can be disabled by setting this bit to one.
Bit 4: Disable parameter freeze on trip
If this bit is 0 then the parameters listed below are frozen on trip until the trip is cleared. If this bit is 1 then this feature is disabled.
H42 Drive Name Characters 9-12
Mode Open-Loop, RFC-A, RFC-S
Minimum -2147483648 Maximum 2147483647
Default 0 Units
Type 32 Bit User Save Update Rate N/A
Display Format String Decimal Places 0
Coding RW, PT
H43 Drive Name Characters 13-16
Mode Open-Loop, RFC-A, RFC-S
Minimum -2147483648 Maximum 2147483647
Default 0 Units
Type 32 Bit User Save Update Rate N/A
Display Format String Decimal Places 0
Coding RW, PT
H45 Action On Trip Detection
Mode Open-Loop, RFC-A, RFC-S
Minimum
0
(Display: 00000)
Maximum
31
(Display: 11111)
Default
0
(Display: 00000)
Units
Type 8 Bit User Save Update Rate Background read
Display Format Binary Decimal Places 0
Coding RW