Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
User Menu A Commissioning
Advanced
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
E300 Design Guide 323
Issue Number: 1
If Number Of Autoreset Attempts (H46) = 0 then no auto-reset attempts are made. Any other value will cause the drive to automatically reset following
a trip for the number of times programmed after a delay defined by Auto-reset Delay (H47) subject to the minimum reset time allowed for the type of
trip. Note that for some trips the minimum is 10 s. The auto-reset count is only incremented when the trip is the same as the previous trip otherwise it
is reset to 0. When the auto-reset count reaches the programmed value, any further trip of the same value will not cause an auto-reset. If the number
of auto-reset attempts defined by Number Of Autoreset Attempts (H46) has not been reached and there has been no trip for 5 minutes then the auto-
reset count is cleared. Auto reset will not occur after any trips with priority levels 1, 2 or 3 as defined in Trip 0 (L29). When a manual reset occurs the
auto-reset counter is reset to zero.
If Number Of Autoreset Attempts (H46) = 6 the auto-reset counter is held at zero, and so there is no limit on the number of auto-reset attempts.
See Number Of Autoreset Attempts (H46).
Open-loop mode RFC-A or RFC-S modes
Speed Error (J31)
Speed Loop Output (J32)
Total Output Current (J22) Total Output Current (J22)
Torque Producing Current (J24) Torque Producing Current (J24)
Magnetizing Current (J25) Magnetizing Current (J25)
Output Frequency (J60) Output Frequency (J60)
Output Voltage (J61) Output Voltage (J61)
Output Power (J59) Output Power (J59)
D.c. Bus Voltage (J65) D.C. Bus Voltage (J65)
T5 T6 Analog Input 1 (F35) T5 T6 Analog Input 1 (F35)
T7 Analog Input 2 (F36) T7 Analog Input 2 (F36)
T8 Analog Input 3 (F37) T8 Analog Input 3 (F37)
H46 Number Of Autoreset Attempts
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 6
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
0 None
11
22
33
44
55
6 Infinite
H47 Auto-reset Delay
Mode Open-Loop, RFC-A, RFC-S
Minimum 1.0 Maximum 600.0
Default 1.0 Units s
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW