Firmware Version (J04) displays the drive software version number as a decimal number wwxxyyzz. A keypad will display the value in this parameter
as ww.xx.yy.zz.
Maximum Heavy Duty Rating (J05) defines the maximum setting for Motor Rated Current (B02) that gives heavy duty operation. If Maximum Heavy
Duty Rating (J05) = 0.000 then heavy duty operation is not possible. If Maximum Heavy Duty Rating (J05) = VM_RATED_CURRENT[MAX] then
normal duty operation is not possible.
Drive Full Scale Current Kc (J06) shows the full scale current in rms Amps. If the drive current exceeds this level it will cause an over current trip.
14
Contactor control
Generate motor contactor control output.
Exit to state 0:
Fast Disable (B27) = Off (0) AND
•Total Output Current (J22) <
25 % of rated current AND
F10 T31 STO Input 1 State (F10)= Off (0) AND
There is no digital speed signal present (if used) AND
There is no direction signal present (in dual direction signal mode) AND
The Fast disable input (if used) = Off (0) OR
The drive trips
The following error detection is made in this state after 4 s. The list is in order of priority:
1. If Motor Contactor Monitoring Enable (B29)= On (1), and it takes > 4 s for the monitoring input to be set to 0, generate a Trip 71 (Mot con
closd).
2. If the Fast Disable (B27) input terminal = On (1), then generate Trip 65 (Fast disable err).
3. If the F10 T31 STO Input 1 State (F10) = On 1, then generate Trip 66 (STO Ctrl err).
4. If the total current is > 25 % of rated, then generate Trip 67 (Current on stop).
J04 Firmware Version
Mode RFC-A
Minimum 0 Maximum 99999999
Default Units A
Type 32 Bit Volatile Update Rate Power-up write
Display Format Version Decimal Places 0
Coding RO, ND, NC, PT
J05 Maximum Heavy Duty Rating
Mode RFC-A
Minimum 0.000 Maximum 99999.999
Default Units A
Type 32 Bit Volatile Update Rate Power-up write
Display Format Standard Decimal Places 3
Coding RO, ND, NC, PT
J06 Drive Full Scale Current Kc
Mode Open-Loop, RFC-A, RFC-S
Minimum 0.000 Maximum 99999.999
Default Units A
Type 32 Bit Volatile Update Rate Power-up write
Display Format Standard Decimal Places 3
Coding RO, ND, NC, PT
J07 Drive Rated Voltage
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 3
Default Units
Type 8 Bit Volatile Update Rate Power-up write
Display Format Standard Decimal Places 0
Coding RO, TE, ND, NC, PT