Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
User Menu A Commissioning
Advanced
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
E300 Design Guide 371
Issue Number: 1
Parameter
Range(Ú) Default(Ö)
Type
Open-Loop RFC-A RFC-S Open-Loop RFC-A RFC-S
K01 Logic Function 1 Output Off (0) or On (1)
RO Bit ND NC PT
K02 Logic Function 1 Source 1 A00 to AB99 A00 RW Num PT US
K03 Logic Function 1 Source 1 Invert Off (0) or On (1) Off (0) RW Bit US
K04 Logic Function 1 Source 2 A00 to AB99 A00 RW Num PT US
K05 Logic Function 1 Source 2 Invert Off (0) or On (1) Off (0) RW Bit US
K06 Logic Function 1 Output Invert Off (0) or On (1) Off (0) RW Bit US
K07 Logic Function 1 Delay ±25.0 s 0.0 s RW Num US
K08 Logic Function 1 Destination A00 to AB99 A00 RW Num DE PT US
K09 Logic Function 2 Output Off (0) or On (1)
RO Bit ND NC PT
K10 Logic Function 2 Source 1 A00 to AB99 A00 RW Num PT US
K11 Logic Function 2 Source 1 Invert Off (0) or On (1) Off (0) RW Bit US
K12 Logic Function 2 Source 2 A00 to AB99 A00 RW Num PT US
K13 Logic Function 2 Source 2 Invert Off (0) or On (1) Off (0) RW Bit US
K14 Logic Function 2 Output Invert Off (0) or On (1) Off (0) RW Bit US
K15 Logic Function 2 Delay ±25.0 s 0.0 s RW Num US
K16 Logic Function 2 Destination A00 to AB99 A00 RW Num DE PT US
K17 Binary Sum Ones Off (0) or On (1) Off (0) RW Bit NC
K18 Binary Sum Twos Off (0) or On (1) Off (0) RW Bit NC
K19 Binary Sum Fours Off (0) or On (1) Off (0) RW Bit NC
K20 Binary Sum Output 0 to 255
RO Num ND NC PT
K21 Binary Sum Destination A00 to AB99 A00 RW Num DE PT US
K22 Binary Sum Offset 0 to 248 0 RW Num US
K23 Threshold Detector 1 Output Off (0) or On (1)
RO Bit ND NC PT
K24 Threshold Detector 1 Source A00 to AB99 A00 RW Num PT US
K25 Threshold Detector 1 Level 0.00 to 100.00 % 0.00 % RW Num US
K26 Threshold Detector 1 Hysteresis 0.00 to 25.00 % 0.00 % RW Num US
K27
Threshold Detector 1 Output
Invert
Off (0) or On (1) Off (0) RW Bit US
K28 Threshold Detector 1 Destination A00 to AB99 A00 RW Num DE PT US
K29 Variable Selector 1 Output ±100.00 %
RO Num ND NC PT
K30 Variable Selector 1 Source 1 A00 to AB99 A00 RW Num PT US
K31 Variable Selector 1 Source 2 A00 to AB99 A00 RW Num PT US
K32 Variable Selector 1 Mode
Input 1 (0), Input 2 (1), Add (2), Subtract (3),
Multiply (4), Divide (5), Time Const (6), Ramp (7),
Modulus (8), Powers (9), Sectional (10)
Input 1 (0) RW Txt US
K33 Variable Selector 1 Destination A00 to AB99 A00 RW Num DE PT US
K34
Variable Selector 1 Source 1
Scaling
±4.000 1.000 RW Num US
K35
Variable Selector 1 Source 2
Scaling
±4.000 1.000 RW Num US
K36 Variable Selector 1 Control 0.00 to 100.00 0.00 RW Num US
K37 Variable Selector 1 Enable Off (0) or On (1) On (1) RW Bit US
K38 Threshold Detector 2 Output Off (0) or On (1)
RO Bit ND NC PT
K39 Threshold Detector 2 Source A00 to AB99 A00 RW Num PT US
K40 Threshold Detector 2 Level 0.00 to 100.00 % 0.00 % RW Num US
K41 Threshold Detector 2 Hysteresis 0.00 to 25.00 % 0.00 % RW Num US
K42
Threshold Detector 2 Output
Invert
Off (0) or On (1) Off (0) RW Bit US
K43 Threshold Detector 2 Destination A00 to AB99 A00 RW Num DE PT US
K44 Variable Selector 2 Output ±100.00 %
RO Num ND NC PT
K45 Variable Selector 2 Source 1 A00 to AB99 A00 RW Num PT US
K46 Variable Selector 2 Source 2 A00 to AB99 A00 RW Num PT US
K47 Variable Selector 2 Mode
Input 1 (0), Input 2 (1), Add (2), Subtract (3),
Multiply (4), Divide (5), Time Const (6), Ramp (7),
Modulus (8), Powers (9), Sectional (10)
Input 1 (0) RW Txt US
K48 Variable Selector 2 Destination A00 to AB99 A00 RW Num DE PT US
K49
Variable Selector 2 Source 1
Scaling
±4.000 1.000 RW Num US
K50
Variable Selector 2 Source 2
Scaling
±4.000 1.000 RW Num US
K51 Variable Selector 2 Control 0.00 to 100.00 0.00 RW Num US
K52 Variable Selector 2 Enable Off (0) or On (1) On (1) RW Bit US