430 E300 Design Guide
           Issue Number: 1
See Data Logger Trigger (Y06).
Single (0):
If Data Logger Arm (Y11) is set to 1 the scope starts to acquire pre-trigger data (i.e. enough data to provide information for the pre-trigger period) and 
Data Logger Data Not Ready (Y12) is set to 1. The scope can then be triggered on the next trigger event (i.e. a rising edge on the trigger input of the 
main scope block). Note that the scope can only be triggered once the required amount of pre-trigger data has been sampled. Failure to do this will 
result in the scope function not triggering correctly. When the trigger event occurs Data Logger Arm (Y11) is set to 0, and when the post-trigger data 
has been stored Data Logger Data Not Ready (Y12) is set to 0. If Autosave Mode (Y17) is non-zero, the data in the scope trace buffer is saved to a 
non-volatile media card fitted in the drive. When the save is complete (or data cannot be saved, i.e. no card installed or no space left) the scope is 
ready again to receive data. If Data Logger Arm (Y11) is set to 1 the scope will start to acquire data again.
It is possible to read scope files via comms or into an option module. However, scope file transfer can only be initiated when Data Logger Arm (Y10) 
= 0, Data Logger Data Not Ready (Y12) = 0, Data Logger Saving Data (Y13) = 0 and at least one trace has been set up. While the file transfer is in 
progress Data Logger Saving Data (Y13) is set to 1.
The scope system is reset under any of the following conditions: 
1. At power-up.
2. If the drive is reset when Data Logger Trace 1 Source (Y02) to Data Logger Trace 4 Source (Y05) have been modified.
3. The drive mode is changed.
4. If Data Logging Mode (Y10), Data Logger Sample Time (Y14) or Data Logger Trigger Delay (Y15) are modified.
When the scope is reset Data Logger Arm (Y11) is reset to 0 and the trace data is all cleared to 0.
Normal (1):
The scope operates in the same way as single mode except that Data Logger Arm (Y11) is automatically set back to 1 after a time delay of 1s once 
the post-trigger data has been acquired, and the scope dat
a has been saved to a n
on-volatile media card if Autosave Mode (Y17) > 0.
Y09 Data Logger Trigger Invert
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
Y10 Data Logging Mode
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 2
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, Txt
Value Text
0 Single
1Normal
2Auto
Arm ()
Y10
Data Logger Data
Not Ready ()
Y11
Data Logger Saving
Data (
Y12)
Main scope block
trigger input
Data Logging Mode Auto-save Mode ( ) = Single (0) and   ( ) > 0
Y09 Y16
Acquiring post
trigger data
Acquiring pre-
trigger data
Saving data to
NV media card