EasyManuals Logo

Emotron AFR 2.0 Series User Manual

Emotron AFR 2.0 Series
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
150 Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-7318-01r1
PF Comm Err * Internal communication error Contact service
PF Int Temp * Internal temperature too high Check internal fans
PF Temp Err * Malfunction in temperature sensor Contact service
Supply error No synchronisation current pulse detected
- Check mains supply voltage
- Check LCL-filter and cables
- Check Circuit breaker and main contactor
Sup Chk Err
Actual supply frequency or phase sequence
does not correspond to the settings in
respective menus [O12] and [O14].
- Check mains supply voltage
- Check LCL-filter and cables
- Check Circuit breaker and main contactor
- Check wiring of the voltage sensor (if “Sync option” is
used)
- Re-do supply ID-Run.
Sync Error Overcurrent during synchronisation to supply
- Check mains supply voltage
- Check LCL-filter and cables
- Check Circuit breaker and main contactor
- Check supply parameters [O11]-[O14]
- Check if DC-link is not already loaded (check if any
load drawing current from DC-link).
AutoID Error
Failure during ID run
-Supply could not be identified
- Check corresponding Digital Input signal is high if
enable signal is set in DigIn setting menu [520].
Sup U Err Too much deviation in supply voltage.
- Check mains supply voltage
- Check wiring of synchronization option board (voltage
measurement board) if used.
- Check if supply/grid voltage fluctuating too much.
Sup F Err Too much deviation in supply voltage.
- Check mains supply voltage
- Check wiring of synchronization option board (voltage
measurement board) if used.
- Check if supply/grid voltage fluctuating too much.
Sensor Err
Supply voltage measurement board is not
configured/connected properly.
- Check and verify all the required settings for supply
voltage measurement board.
- Check the wiring connections required for supply
voltage measurement board.
GCP 3U>
Monitored grid voltage is higher than the
corresponding trip level setting.
- Check if the trip level settings are realistic.
- Check the mains supply wiring.
- Check the connection wiring of supply voltage
measurement board.
- Check the drive nominal settings are according to the
connected supply/grid.
GCP 3U>>
Monitored grid voltage is higher than the
corresponding trip level setting.
- Check if the trip level settings are realistic.
- Check the mains supply wiring.
- Check the connection wiring of supply voltage
measurement board.
- Check the drive nominal settings are according to the
connected supply/grid.
GCP 3U<
Monitored grid voltage is lower than the
corresponding trip level setting.
- Check if the trip level settings are realistic.
- Check the mains supply wiring.
- Check the connection wiring of supply voltage
measurement board.
- Check the drive nominal settings are according to the
connected supply/grid.
GCP 3U<<
Monitored grid voltage is lower than the
corresponding trip level setting.
- Check if the trip level settings are realistic.
- Check the mains supply wiring.
- Check the connection wiring of supply voltage
measurement board.
- Check the drive nominal settings are according to the
connected supply/grid.
Table 29 Trip condition, their possible causes and remedial action
Trip condition Possible Cause Remedy

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron AFR 2.0 Series and is the answer not in the manual?

Emotron AFR 2.0 Series Specifications

General IconGeneral
BrandEmotron
ModelAFR 2.0 Series
CategoryIndustrial Electrical
LanguageEnglish