Emotron AB 01-4429-01r2 Functional Description 117
Fig. 93
AnIn1 Enable [513A]
Parameter for enable/disable analogue input selection via
digital inputs (DigIn set to function AnIn Select).
Communication information
AnIn2 Function [514]
Parameter for setting the function of Analogue Input 2.
Same function as AnIn1 Func [511].
Communication information
AnIn2 Setup [515]
Parameter for setting the function of Analogue Input 2.
Same functions as AnIn1 Setup [512].
Communication information
AnIn2 Advanced [516]
Same functions and submenus as under AnIn1 Advanced
[513].
Communication information
AnIn3 Function [517]
Parameter for setting the function of Analogue Input 3.
Same function as AnIn1 Func [511].
Communication information
Default: On
On 0 AnIn1 is always active
!DigIn 1 AnIn1 is only active if the digital input is low.
DigIn 2 AnIn1 is only active if the digital input is high.
Modbus Instance no/DeviceNet no: AnIn1 43210
Profibus slot/index AnIn1 169/114
Fieldbus format UInt
Modbus format UInt
Default: Off
Selection: Same as in menu
[511]
Modbus Instance no/DeviceNet no: 43211
Profibus slot/index 169/115
Fieldbus format UInt
Modbus format UInt
AnIn change
100%
63%
Original input signal
Filtered AnIn signal
T
5 X T
Default: 4 – 20 mA
Dependent on Setting of switch S2
Selection: Same as in menu
[512].
Modbus Instance no/DeviceNet no: 43212
Profibus slot/index 169/116
Fieldbus format UInt
Modbus format UInt
Modbus Instance no/DeviceNet no:
43213–43220
43542
43552
Profibus slot/index
169/117–124
170/191
170/201
Default: Off
Selection: Same as in menu
[511]
Modbus Instance no/DeviceNet no: 43221
Profibus slot/index 169/125
Fieldbus format UInt
Modbus format UInt
515 AnIn2 Setup
Stp 4-20mA