Emotron AB 01-4429-01r2 Functional Description 75
External Motor Temperature [25R]
Delay time starts counting when the fault disappears. When
the time delay has elapsed, the alarm will be reset if the func-
tion is active.
Communication information
External Motor Trip Type [25S]
Select the preferred way to react to an alarm trip.
Communication information
Liquid cooling low level [25T]
Delay time starts counting when the fault disappears. When
the time delay has elapsed, the alarm will be reset if the func-
tion is active.
Communication information
Liquid Cooling Low level Trip Type [25U]
Select the preferred way to react to an alarm trip.
Communication information
11.2.8 Serial Communication [260]
This function is to define the communication parameters for
serial communication. There are two types of options availa-
ble for serial communication, RS232/485 (Modbus/RTU)
and fieldbus modules (Profibus, DeviceNet and Ethernet).
For more information see chapter Serial communication and
respective option manual.
Comm Type [261]
Select RS232/485 [262] or Fieldbus [263].
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Modbus Instance no/DeviceNet no: 43097
Profibus slot/index 168/239
Fieldbus format Long, 1=1 s
Modbus format EInt
Default: Trip
Selection: Same as menu [25B]
Modbus Instance no/DeviceNet no: 43098
Profibus slot/index 168/240
Fieldbus format UInt
Modbus format UInt
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Modbus Instance no/DeviceNet no: 43099
Profibus slot/index 169/3
Fieldbus format Long, 1=1 s
Modbus format EInt
Default: Trip
Selection: Same as menu [25B]
Modbus Instance no/DeviceNet no: 43100
Profibus slot/index 169/4
Fieldbus format UInt
Modbus format UInt
Default: RS232/485
RS232/485 0 RS232/485 selected
Fieldbus 1
Fieldbus selected (Profibus, DeviceNet or
Modbus/TCP)
NOTE: Toggling the setting in this menu will perform a
soft reset (re-boot) of the Fieldbus module.
261 Com Type
Stp RS232/485