168 CG Drives & Automation 01-7492-01r1
Analogue Comparator 1, Level Low [6113]
Sets the analogue comparator low level, with unit and range
according to the selected value in menu [6111].
Analogue Comparator 1, Type [6114]
Selects the analogue comparator type, i.e. Hysteresis or
Window type. See fig. 134 and fig. 135.
Analogue Comparator 1, Polarity [6115]
Selects how the selected value in [6111] should be handled
prior to the analogue comparator , i.e. as absolute value or
handled with sign. See fig. 134
Example
See fig. 134 and fig. 135 for different principle
functionality of comparator features 6114 and 6115.
Fig. 134 Principle functionality of comparator features for
“Type [6114] = Hysteresis ”and “Polar [6115]”.
Table 40 Comments to fig. 133 regarding Window selection.
No. Description
Window
1
The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set
high.
2
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
3
The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set
high.
4
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
5
The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set
high.
6
The reference signal passes the Level HI
value from below (signal outside Window
band),the comparator CA1 is reset, output is
set low.
7
The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set
high.
8
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
6113 CA1 LevelLO
Default: 200 rpm
Range: Range as [6112].
6114 CA1 Type
Default: Hysteresis
Hysteresis 0 Hysteresis type comparator
Window 1 Window type comparator
6115 CA1 Polar
Default: Unipolar
Unipolar 0 Absolute value of [6111] used
Bipolar 1 Signed value of [6111] used
Type [6114]= Hysteresis
[6115] Unipolar
[6115] Bipolar
[6115] Bipolar
[6115] Bipolar
[6112] HI > 0
[6113] LO > 0
[6112] HI > 0
[6113] LO > 0
[6112] HI > 0
[6113] LO < 0
[6112] HI < 0
[6113] LO < 0
An.Value
[6111]
An.Value
[6111]
An.Value
[6111]
An.Value
[6111]
CA1
CA1