Cubemass DCI MODBUS RS485 Wiring
Endress+Hauser 23
A0002591
Fig. 14: Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(14 AWG)
A View A (field housing)
C View C (wall-mount housing)
a Connection compartment cover
b Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
c Ground terminal for protective ground
d Fieldbus cable
Terminal No. 26: A (RxD/TxD-P)
Terminal No. 27: B (RxD/TxD-N)
e Ground terminal for signal cable shield/fieldbus cable shield
Observe the following:
the shielding and grounding of the fieldbus cable ä 20
that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f Service adapter for connecting service interface 193 (Fieldcheck, FieldCare)
g Signal cable: terminal assignment ä 24