Wiring Cubemass DCI MODBUS RS485
22 Endress+Hauser
4.3 Connecting the measuring unit
4.3.1 Transmitter connection
#
Warning!
Risk of electric shock. Switch off the power supply before opening the device.
Do not install or wire the device while it is connected to the power supply.
Failure to comply with this precaution can result in irreparable damage to the electronics.
Risk of electric shock. Connect the protective ground to the ground terminal on the housing
before the power supply is applied unless special protection measures have been taken (e. g.
galvanically isolated power supply SELV or PELV).
Compare the specifications on the nameplate with the local supply voltage and frequency.
The national regulations governing the installation of electrical equipment also apply.
1. Remove the cover of the connection compartment (a) from the transmitter housing.
2. Feed the power supply cable (b), signal cable (g) and fieldbus cable (d) through the appropriate
cable entries.
3. Perform wiring in accordance with the respective terminal assignment and the associated
wiring diagram.
"
Caution!
Risk of damaging the fieldbus cable!
Observe the information about shielding and grounding the fieldbus cable ( ä 20).
We recommend that the fieldbus cable not be looped using conventional cable glands. If
even just one measuring device is subsequently replaced, the bus communication will have
to be interrupted.
4. Screw the cover of the connection compartment (a) firmly onto the transmitter housing.