Commissioning Proline Promass 83 PROFIBUS DP/PA
100 Endress+Hauser
6.7.4 Configuration examples with Simatic S7 HW-Konfig
Example 1:
a0002662
Fig. 45: Complete configuration using the Promass 83 GSD file (manufacturer-specific GSD file)
It is essential to adhere to the following sequence when configuring the modules into the
automation system (PROFIBUS class 1 master):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1AI 5Analog Input function block 1
Output variable Mass flow (factory setting)
Data structure Page 90
2AI 5Analog Input function block 2
Output variable Volume flow (factory setting)
Data structure Page 90
3AI 5Analog Input function block 3
Output variable Corrected volume flow (factory setting)
Data structure Page 90
4AI 5Analog Input function block 4
Output variable Density (factory setting)
Data structure Page 90
5AI 5Analog Input function block 5
Output variable Reference density (factory setting)
Data structure Page 90
6AI 5Analog Input function block 6
Output variable Temperature (factory setting)
Data structure Page 90