5.6.2 Configuring the device address
The address must always be configured for a PROFIBUS DP/PA device. The valid device addresses
are in the range from 0…125. In a PROFIBUS DP/PA network, each address can only be assigned
once. If an address is not configured correctly, the device is not recognised by the master. The
address 126 can be used for initial commissioning and for service purposes.
Addressing via local operation
Page 40
Addressing via miniature switches
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1. Loosen Allen screw (3 mm) of the securing clamp.
2. Unscrew cover of the electronics compartment from the transmitter housing.
3. Remove the local display (if present) by loosening the fixing screw of the display module.
4. Set the position of the miniature switches on the I/O board using a sharp pointed object.
5. Installation is the reverse of the removal procedure.
a0002590
Fig. 30: Addressing with the aid of miniature switches on the I/O board
a Miniature switches for setting the device address (illustrated: 1 + 16 + 32 = device address 49)
b Miniature switches for the address mode (method of addressing):
OFF = software addressing via local operation (factory setting)
ON = hardware addressing via miniature switches
c Miniature switches not assigned
OFF ON
11
7
22
8
43
84
165
326
64
b
a
OFF ON