6.7.3 Configuration information for integrating modules
Promass 83 is a modular PROFIBUS slave. In contrast to a compact slave, the structure of a modular
slave is variable - it consists of several individual modules. In the GSD file, the individual modules
are described with their individual properties. The modules are permanently assigned to the slots,
i.e. the sequence or arrangement of the modules must be observed when configuring the modules
(see following table). Gaps between configured modules have to be assigned the
“EMPTY_MODULE” module.
To optimise the data throughput rate of the PROFIBUS DP network, it is recommended to only
configure modules that are processed in the PROFIBUS master system.
It is essential to adhere to the following sequence/assignment when configuring the modules in the
PROFIBUS master system:
!
Note!
• The assignment of the measured variables for the Analog Input function blocks (1...6) and the
Totalizer function blocks (1...3) can be changed by means of the “CHANNEL” parameter.
• The device has to be reset once a new configuration has been loaded to the automation system.
This can be effected as follows:
–Local display
– By means of a class 2 master (e.g. Fieldcare)
– Switching supply voltage OFF and then ON again.
Slot
sequence
Module Description
1AIAnalog Input function block 1
Output variable → Mass flow (factory setting)
2AIAnalog Input function block 2
Output variable → Volume flow (factory setting)
3AIAnalog Input function block 3
Output variable → Corrected volume flow (factory setting)
4AIAnalog Input function block 4
Output variable → Density (factory setting)
5AIAnalog Input function block 5
Output variable → Reference density (factory setting)
6AIAnalog Input function block 6
Output variable → Temperature (factory setting)
7
TOTAL or
SETTOT_TOTAL or
SETTOT_MODETOT_TOTAL
Totalizer function block 1
Output variable for TOTAL → Mass flow (factory setting)
Totalizer configuration → Page 94
8 Totalizer function block 2
Output variable for TOTAL → Mass flow (factory setting)
Totalizer configuration → Page 94
9 Totalizer function block 3
Output variable for TOTAL → Mass flow (factory setting)
Totalizer configuration → Page 94
10 DISPLAY_VALUE Default value for local display
11 CONTROL_BLOCK Control of device functions
12 BATCHING_QUANTITY Batching quantity
13 BATCHING_FIX_COMP_QUANTITY Fixed compensation quantity