Proline Promass 83 PROFIBUS DP/PA Wiring
Endress+Hauser 37
Technical data (fieldbus connector):
4.4 Degree of protection
The devices fulfill all the requirements for IP 67.
Compliance with the following points is mandatory following installation in the field or servicing,
in order to ensure that IP 67 protection is maintained:
• The housing seals must be clean and undamaged when inserted into their grooves. The seals must
be dried, cleaned or replaced if necessary.
• All threaded fasteners and screw covers must be firmly tightened.
• The cables used for connection must be of the specified outside diameter. → Page 30
• Firmly tighten the cable entries.
• The cables must loop down before they enter the cable entries (“water trap”). This arrangement
prevents moisture penetrating the entry. Always install the measuring device in such a way that
the cable entries do not point up.
• Remove all unused cable entries and insert plugs instead.
• Do not remove the grommet from the cable entry.
a0001914
Fig. 22: Installation instructions, cable entries
Connection cross section 0.75 mm
2
Connector thread PG 13.5
Degree of protection IP 67 in accordance with DIN 40 050 IEC 529
Contact surface CuZnAu
Housing material Cu Zn, surface Ni
Flammability V - 2 in accordance with UL - 94
Operating temperature –40...+85 °C
Ambient temperature –40...+150 °C
Nominal current per contact 3 A
Nominal voltage 125...150 V DC in accordance with the VDE Standard 01 10/ISO Group 10
Resistance to tracking KC 600
Volume resistance ≤ 8 mΩ in accordance with IEC 512 Part 2
Insulation resistance ≤ 10
12
Ω in accordance with IEC 512 Part 2