Technical data
4
Rivo™ I Controller EN
21
Evoqua Water Technologies GmbH | W3T597263 Issue 01-0624
4 TECHNICAL DATA
4.1 Electronics Module
Rivo™ I Controller electronics module (Mod. E10)
Article number W3T570784
Area of application Treatment of drinking water and waste water, the treatment of industrial and process water,
cooling water circuits
Housing Dimensions (WxHxD) 220 x 305 x 153 mm
Weight approx. 3.7 kg
Protection rating IP66
Mains connection • 100 ... 240 V AC ± 10% 50 ... 60 Hz or 24 V DC
• -15 ... +20 %, 15 W
Display 4.3” graphic color display with backlit LED and resistive touchscreen
Insulation Overvoltage category 2
Contamination level 2
Protection category 1
Approvals CE, CSA
Operating conditions Ambient temperature 0 ... 50 °C (32 ... 122 °F)
Relative humidity < 80 %, non-condensing, moist environment
Environment No direct sunlight, use indoors
Atmospheric pressure 75 ... 106 kPa
Max. working height (altitude) 2000 m
Ambient noise <45 dB