Description and function
6
Rivo™ I Controller EN
41
Evoqua Water Technologies GmbH | W3T597263 Issue 01-0624
6.14 Messages and alarms
Alarms, warnings, messages are displayed by means of a
colored message symbol ( alarm bell) and a RGB LED
above the display.
Tap the alarm bell to open the message window. All active
messages are displayed with text. Acknowledgeable mes-
sages are confirmed or acknowledged with the ACK but-
ton.
6.14.1 Configuration
The electronics module supports the creation of freely
configurable alarms. The alarms are output optionally via
relay contacts and a color message display. At the same
time, a message is displayed in the message system. The
number of available relays depends on the configuration.
The alarm relays can be used, for example, for safety
deactivation of dosing when specific values are exceeded
or not reached. The assignment of a relay as a switching
function is optional.
Each alarm can be configured as described below. Multi-
ple assignment is possible:
Red symbol: error active
Yellow symbol: warning active
Neutral symbol: general notes
Message freely configurable text
Description freely configurable text
Delay time hh:mm:22
00:00:00 to 10:49:59
Notification level Error/warning
Acknowledge Without/simple ACK/ACK
with reset
Assignment Single/multiple assignment
Relay assignment Assignment to relay