Description and function
EN Rivo™ I Controller
42
W3T597263 Issue 01-0624 | Evoqua Water Technologies GmbH
6.14.2 Without Acknowledge
The alarm symbol and the message symbol light up in
the event of an alarm and go out automatically when
the condition is eliminated.
Unlatched alarms are displayed in yellow as mes-
sages.
The relay is active when the alarm symbol is dis-
played and the alarm is active.
6.14.3 ACK with reset
In the event of an alarm, the alarm symbol and the
message symbol flash and the relay is active until
acknowledged.
The alarm symbol and the message go out even if the
conditions still apply when the alarm is acknowl-
edged.
Latched alarms are displayed in red as messages.
The relay becomes inactive after acknowledgment if
the condition is still pending.
6.14.4 Simple ACK
The relay becomes active as soon as the alarm is
active.
In the event of an alarm, the alarm symbol and the
message symbol flash until the alarm is acknowl-
edged.
If the condition is no longer present when the alarm is
acknowledged, the alarm symbol goes out and the
message disappears.
If the condition is still present when the alarm is
acknowledged, the alarm symbol and the message
are reset from flashing to a permanent state. The
alarm symbol and the message light up until the con-
dition is eliminated (auto-reset).
Latched alarms are displayed in red as messages.
The relay is only deactivated when the condition has
been eliminated and acknowledged.