Installation
7
Rivo™ I Controller EN
49
Evoqua Water Technologies GmbH | W3T597263 Issue 01-0624
7.1 Requirements with regard to the environment
and installation location
The installation location must meet the following require-
ments:
• The installation location must not be accessible to the
public.
• The installation location must be such that operation
by unauthorized personnel is ruled out.
• The installation location must not be used as a per-
manent workplace.
• Protect the device against moisture, rain, frost, heat
and direct sunlight.
• Do not install the device outdoors.
• Do not expose the device to strong vibration or
impact, magnetic fields or electromagnetic radiation.
• Provide sufficient aeration and ventilation.
• Note the minimum ceiling height.
• The installation wall must be vertical, flat and stable.
• The device must be accessible and visible from the
front and side for installation, operation and mainte-
nance.
• Operating and ambient temperature must lie between
0 and +50 °C (32 ... 122 °F) (technical data).
• The air in the room must be non-condensing.
• The Electronics Module is not suitable for electrical
connection with permanently installed cable conduits.
If the cable glands do not meet local installation rules
and regulations, these glands must be replaced with
suitable ones.
WARNING
Danger caused by fire or explosive material
Possible consequence: fatal or serious injury.
• Do not use the device in environments where
there are flammable gases, fumes or dust or
conductive dust.
• Smoking, fire, naked flames, welding, and
work that may generate sparks are forbidden
in the vicinity of the device.