4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
4−3
Festo P.BE−CPEA−CL−E N en 0711a
4.1 Function of the input modules CP−E16−M...−EL and CP−E32−M8−EL
CPI input modules provide digital inputs for connecting sen
sors, thereby enabling e.g.cylinder positions to be scanned.
A distinction is made between the following types:
Product illustration
Type Explanation
Sensor connections via 16 M8 sockets, 4−pin
CP−E32−M8−EL Provides 32 PNP inputs (IP65).
It can only be connected to the CPI system with
extended functions (CPI master). The CP module
CP−E32−M8−EL enables module diagnosis and
module monitoring of the sensor voltage.
Sensor connections via 16 M8 sockets, 3−pin
CP−E16−M8−EL Provides 16 PNP inputs (IP65). CP module
CP−E16−M8−EL enables group diagnosis and group
monitoring of the sensor voltage. A group consists
of 4 inputs.
Sensor connections via 8 M12 sockets, 5−pin
CP−E16−M12−EL Provides 16 PNP inputs (IP65).
CP module CP−E16−M8−EL enables group diagnosis
and group monitoring of the sensor voltage.
A group consists of 4 inputs.
Tab.4/1: Over view of input modules