B. Glossary
B-6
Festo P.BE-CPX-PNIO-E N en 1407c English
Restrictions Crosso ver detectio n is not avail able in Remote I/O operating
mode with additional function Prioritized S tart-up” (FSU):
Use an appropriate cabl e (see secti o n 1.6.2).
Make sure that the function Autonegotiation/Autocros-
sover” is deactivated in your control software before pla-
cing the system in operation (see section 2.6.4).
If necessary, the function Autonegotiation/Autocrossov-
er” must also be deactiva ted on the hardware-si de, in the
basic setting of your controller (PLC) or switches or
routers in between: ch eck the port settings for this pur-
pose.
The additional function FSU has restrictions in parameterisa-
tion:
Module parameters cannot be set over the controller soft-
ware and must therefore be entered using CPX-FMT or
CPX-MMI.
For the system start, the function “System Start with
Saved Parameters” (“Saved” or “Stored” parameters)
must be activated to ensure that the parameters entered
using FMT or MMI are used.
Additional information on parameterisatio n can be found in
the corresponding sections, especially section 2.8.