EasyManua.ls Logo

Festo CPX-FB33 - Page 85

Festo CPX-FB33
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Commissioning
2-37
Festo P.BE-CPX-PNIO-EN en 1407c English
10. Make sure that the follow i ng values are set for “IO Cycle”:
Update time 2:
–Mode: fixed
Update time
Update time: 1,000 ms
Address monitoring time 3:
Number of update cycles: 3
Address monitoring time: 3,000 ms
11. Confirm your inputs by clicking on “OK”.
12. Click on the symbol of the CPX terminal to be configured
in the PR O FINET Hardware Configuratio n (HW Config, 3
in Fig. 2/2).
13. The confi gurati on table is displ ayed:
You will find the configuration table below the schematic
representation of the PROFINET-IO system. If necessary,
increase the size of this area of the HW Config window
(see Fi g. 2/2 or 2 in Fig. 2/11).
14. Double click in the configuration line of the connection
(port) “X1 TP1”.
The window “Properties CPX FSU Port 1” (X1 TP1) is
displayed (see Fig. 2/7).

Table of Contents

Other manuals for Festo CPX-FB33

Related product manuals