2. Commissioning
2-41
Festo P.BE-CPX-PNIO-EN en 1407c English
Observe the basic addressing rules for the allocation of the IP
address, e.g. with respect to the use of private or public ad-
dress ranges. Also check that the IP address can be used in
your automation network (no duplicate address assignment
etc.).
The foll o wing IP address variants are available for addressing
the bus node or CPX terminal:
– factory-specified (“remanent”) IP address (192.168.10.2)
– host system IP address
– dynamic IP address, assigned through DHCP
– static, customer-specific or user-changeabl e IP address.
The dynamic IP address assigned through DCHP can be fixed,
if needed, and so becomes a customer- specific static IP ad-
dress.