16 Addressable Fire Control Panels FC500
26c Connection FC500IP with Flat cable, see
note*(2)
27 Mains indicator LED (switching power supply)
28 Switching-power-supply anchor hole
29 Switching-power-supply output voltage con
-
trol input (connected at factory)
30 Fine trimmer for the Switching-power-supply
output Voltage
31 Auxiliary power-supply terminals (27.6 V)
32 Mains power terminals (110/230V~ 60/50 Hz)
33 Switching-power-supply screws
34 Switching-power-supply fuse — protects aga
-
inst overload:
BAQ140T24 = F 4A 250V
35 Cable: connects the Switching power supply
to the Main board (connected at factory)
35a Voltage switch (110V or 230V)
36 Switching-power-supply anchor
37 Switching-power-supply closure rivet
38 Jack for the User interface board
39 Microprocessor
40 RS232 Serial Port
41 Terminal board
42 Terminal board
43 Jack for the thermal probe
44 Jack for the BAQ140T24 Switching power
supply
45 Battery output voltage control panel (connec-
ted at factory)
46 RS485 terminal board
47 Jack for Extinguishment Module (Future use)
48 Jack (Future use)
49 Jack (Future use)
50 Jumper for Earth Fault (Leakage to Earth)
signalling (Default // ) *(1)
51 Microphone
52 Jack for the connection between User Interfa
-
ce board and the Main board
53 Buzzer
54 Control Panel Backplate
55 38Ah Batteries Backplate
56 Connecting Threaded tube
57 Nuts on Control Panel Backplate
58 Nuts on 38Ah Batteries Backplate
59 12V 38Ah Batteries (accessory item)
(see Figure 16)
*NOTE(1)
Before connecting the Fire control panel to PC for the PC
programming phase, remove the jumper 50 of main bo
-
ard.
After the programming phase is finished, replace the
jumper otherwise the Earth fault (Leakage to Earth) will
not be detected.
+
*(2) If you connect the FC500 IP board with the mot
-
herboard via flat cable (26c) (Fig. 4) the Digital Com
-
municator function will be activated. If the Digital
Communicator function only is requested the
PCLINK cable (26a) and the cables for board power
are not necessary (26b) (see Figure 4). If both Digital
Communicator than PC interface functions are re
-
quested the flat cable and the PCLINK cable are ne
-
cessary, but not the power connection (26b).
!
Be sure that the main voltage is the same of the
input voltage set on the BAQ140T24 power
supplier. Move the switch 35a if the BAQ140T24
input voltage is different from the main voltage,
ONLY when the power supplier is not connec
-
ted to the main power. Please note that the po
-
wer supplier will be damaged if it is connected
to the 230 V main power when it is set for 110 V.