37
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14
flowserve.com
4
Customizing the Actuator
The actuator settings can be customized; i.e., the default settings can be changed and the purchased options can be
configured.
Language selection can also be customized. At the “SETUP IN ENGLISH?” prompt, select “NO” to move between the
following languages: English, Spanish, German, French, Italian, Portuguese, Russian, Malay, Mandarin, Katakana, and
Turkish.
4.1 Changing the Existing Settings
1. Verify main power is ON.
2. Enter the “SETUP” mode as detailed in Section 3.5.3, Entering the Setup Mode.
3. Answer “YES” to “Change Settings.”
4. Enter password if required. See Section 4.2, Password Entry. To change any of the existing settings or to set the
end-of-travel limits for the Open and Close positions of the valve, it may be necessary to enter a password.
5. Answer “YES” or “NO” to each of the following groups of setup data. A “YES” allows the selected setup data group
menu to be displayed. A “NO” moves the user to the next setup data group. For details of each data group, see
Sections 4.2 – 4.27.
• Torque Timer • Local Control
• Valve Setup • ESD Overrides (Emergency Shutdown)
• Operating Time • Inputs
• Torque Setup • Monitor Relay
• Position Setup • Diagnostic Reset
• Modutronic • TAG Number
• DDC (Distributed Digital Control) • LCD Contrast
• FF (Foundation Fieldbus Control) • Password
• PB (Profibus Control) • Motor Thermostat
• DN (DeviceNet Control) • Valve Data
• Status and Alarm Contacts • Port
• Two-Speed Timer • Restricted Setup (Consult Factory)
• Analog Output
• Remote Mode
6. Make changes in each setup group as desired. Each display shows the state or value of the existing settings.
See Figure 4.3.