SENSOR EXCITATION
Type AH/PB/PX Terminal S3: 3 VDC for pulse signals and 1.2 VDC for coil pick-up, I
out
max. 100 μA. This is not a
real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine
wave) or reed switches.
Type PD Terminal P3:
● 8.2 VDC, Iout max. 20 mA
● 12 VDC, Iout max. 30 mA
● 24 VDC, Iout max. 75 mA (varies depending on input supply voltage)
A.2 INPUT
Frequency Minimum 0Hz - maximum 10 kHz for total and flowrate. Maximum frequency depends on signal
type and internal low-pass filter. E.g. reed switch with low-pass filter (max. frequency 120 Hz)
K-Factor 0.000010 - 9,999,999 with variable decimal position
Low-pass filter Available for all pulse signals
Type ZF: Coil
sensitivity
10 mVpp.
Type ZG: Coil
sensitivity
5 mVpp.
RESET TOTAL
Function Terminal input to reset total remotely or to lock the “Clear total” button
Type IB Internally pulled-up switch contact - NPN
Pulse duration 100 msec (minimum)
A.3 OUTPUT
ANALOG OUTPUT
Type AH Galvanically isolated, loop powered 4 – 20 mA output
Accuracy 12 bit. Error 0.03% @ 20°C (Typical 45 ppm/°C).
Can be scaled to any desired range
Supply voltage 10V (lift-off voltage) - 27VDC
Max load 700 ohm @ 24VDC (24V – 10V / 20mA)
COMMUNICATION
Type CX No communication, remote configuration possible with accessory cable (ACE02)
A.4 OPERATIONAL
TOTAL
Digits 7 digits
Unit L, m3, US gal, igal, cf, Oil bbl, kg, ton, US ton, lb or none
Decimals 0 – 1 – 2 or 3
Note Total can be reset to zero
ACCUMULATED TOTAL
Digits 11 digits
Unit decimals According to selection for total
Note Accumulated total cannot be reset to zero