FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 12
[Slide Stop Mode] (If applicable, reference “Compres-
sor Model Differences”) The following are the Slide
Stop mode screen command keys:
[Auto] - The Slide Stop increase and decrease is
under internal control that is based on the differ-
ential of the machines Suction Pressure and Dis-
charge Pressure.
[Manual Increase] - Sends an increase signal for
the duration the key is depressed.
[Manual Decrease] - Sends a decrease signal for
the duration the key is depressed.
[Oil Pump Mode] (If applicable) The following are the
Oil Pump mode screen command keys:
[Auto] - The Oil Pump is started and stopped un-
der internal automatic control.
[Manual On] - Places the Oil Pump in the run mode.
[Manual Off] - Places the Oil Pump in the stop
mode.
If dual pumps were enabled in Factory Setup, then a
toggle key is provided that changes which pump is the
lead, or first pump to be turned on.
[Oil Lead Pump 1] - Selects pump 1 to be the lead
Oil Pump.
[Oil Lead Pump 2] - Selects pump 2 to be the lead
Oil Pump
[Compressor Screen] - Shows the “Compressor
Screen” screen. This screen shows a pictorial of a
compressor and shows the compressor configuration,
operating status and readings.
[Operating Status Page 2] - Shows the second Oper-
ating Status screen.
“OPERATING STATUS - 2” SCREEN
The following information is shown on this display:
Entering Process Temperature - If this temperature
was enabled for monitoring in Panel Setup, it will be
displayed along with the unit of measure. This reading
is used to monitor the temperature of what is being
processed.
Internal Panel Temperature - The main processor
board is equipped with a temperature sensor. The panel
has an operational temperature range that should be
maintained. The operational temperature range is
documented in the specifications document.
Panel Heater - The On or Off message is shown for the
status of the Panel Heater. If the temperature sensor on
the main processor board detects the temperature is
less than or equal to 12 degrees C, the Panel Heater
output is turned on. If the temperature is detected to be
greater than 13 degrees C, the Panel Heater output is
turned off. A temperature of 55 degrees F is attempted to
be maintained.
Battery Status - The status of the battery on the main
processor board is shown. If the battery looses too
much charge, the panel date and time can be lost. The
current voltage reading is shown along with one of the
following messages:
OK - The voltage charge of the battery is fine.
Replace - The voltage charge of the battery is low
and the battery should be replaced.
Power Up Time - The clock time when the Quantum
program was started.
Last Power Down - The clock time when the Quantum
program was last stopped.
Following are the screen key selections for the “Operating
Status - 2” screen:
[Operating Status] - Shows the “Operating Status”
screen.
[Condenser Setpoints] - Shows the “Condenser Con-
trol” screen. This key is shown if a type of Condenser
Control was selected in Panel Setup.
[Compressor Sequence Setpoints] - Shows the “Com-
pressor Sequence Control” screen. This key is shown
if Compressor Sequencing is enabled in Panel Setup.
[Compressor Interlock Setpoints] - Shows the “Com-
pressor Interlock” screen. This key is shown if Com-
pressor Interlock is enabled from the Compressor Se-
quencing option in Panel Setup.