“PROCESS TEMPERATURE CONTROL” SCREEN
CONTROL SETUP - COMPRESSOR SAFETIES SETPOINTS
Compressor safeties are important for the safe operation of
the compressor. The following setpoint screens can be ac-
cessed from this screen:
• Discharge Safeties
• Suction Safeties
• Entering Process Safeties (If applicable)
The following safety setpoint is on this screen:
High Level Shutdown Delay - The time in seconds to
delay after the High Liquid Level input is energized
before the compressor will shut down.