FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 74
ALARMS/SHUTDOWNS MESSAGES
When a Shutdown occurs, the display backlight will flash
on and off to alert an operator of the shutdown. This visual
alarm will help get the attention of the operator in a noisy
engine room environment where audible alarms may not
be heard. Pressing any key on the keypad will clear the
flashing backlight.
Following is a list of all the possible alarms:
Analog Board 1 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Analog Board 1.
Analog Board 2 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Analog Board 2.
Analog Board 3 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Analog Board 3.
Analog Board 4 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Analog Board 4.
Auxiliary #1 Alarm - The Auxiliary #1 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #1 Shutdown - The Auxiliary #1 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #2 Alarm - The Auxiliary #2 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #2 Shutdown - The Auxiliary #2 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #3 Alarm - The Auxiliary #3 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #3 Shutdown - The Auxiliary #3 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #4 Alarm - The Auxiliary #4 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #4 Shutdown - The Auxiliary #4 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #5 Alarm - The Auxiliary #5 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #5 Shutdown - The Auxiliary #5 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #6 Alarm - The Auxiliary #6 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #6 Shutdown - The Auxiliary #6 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #7 Alarm - The Auxiliary #7 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #7 Shutdown - The Auxiliary #7 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Auxiliary #8 Alarm - The Auxiliary #8 input module has
been setup to indicate an alarm when it is deenergized and
it became deenergized.
Auxiliary #8 Shutdown - The Auxiliary #8 input module has
been setup to indicate a shutdown when it is deenergized
and it became deenergized.
Balance Piston Failure Shutdown - Balance piston control
was enabled in Factory Setup. There are 3 conditions that
will cause a “Balance Piston Failure Shutdown”:
1. If the difference between Discharge Pressure and Suc-
tion Pressure is less than 60 lb and the Balance Piston
output module (digital output module 12) is
deenergized, then the Balance Piston pressure must
be 1.1 times Suction Pressure plus or minus 15 lb.
2. If the difference between Discharge Pressure and Suc-
tion Pressure is greater than or equal to 60 lb. and the
Balance Piston output module (digital output module
12) is deenergized, then the Balance Piston pressure
must be 50 lb below Discharge Pressure plus or minus
15 lb.
3. If the Balance Piston output module (digital output mod-
ule 12) is energized, then Balance Piston pressure
must be within 20 lb of Oil Pressure.
Compressor Aux. Failure - This shutdown message is is-
sued if while the compressor is running, the Compressor Aux-
iliary input module, which receives feedback from the motor
starter, becomes deenergized.
Compressor Interlock Failure - This shutdown message
is issued if while the compressor is running the Compres-
sor Auxiliary input module becomes deenergized for five
seconds.
Compressor Starting Failure - Aux. - This shutdown mes-
sage is displayed if after 30 seconds from sending the com-
pressor start command, the compressor auxiliary input mod-
ule is still not energized.
Compressor Starting Failure - Low Motor Amps -
This shutdown message is displayed if after 30 seconds from
sending the compressor start signal, the Motor Amps reading is
not greater than the “Low Motor Amps Shutdown” setpoint.
Compressor Stopping Failure - Aux. - This shutdown mes-
sage is issued if while stopping the compressor, after 8
seconds from the compressor stop command the compres-
sor auxiliary is energized. While this condition is present,
the Oil Pump (if available) is on and Liquid Injection (if
available) is allowed on and the Slide Valve is unloaded to
0% to safeguard the compressor.
Compressor Stopping Failure - Motor Amps - This shut-
down message is issued if while stopping the compressor,

Table of Contents