EasyManua.ls Logo

Frick QUANTUM - Setpoint Box; Capacity Control Box

Frick QUANTUM
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 8
sumed to be PSIG, an entry less than or equal to 29.7 will
cause a message box to appear after pressing the [EN-
TER] key. This message prompts the operator to select
the unit of measure. The operator must select either the
[HG] or the [PSIG] key.
COMMON TERMINOLOGY
Shutdown - A critical safety limit has been reached or ex-
ceeded and the compressor has been shutdown.
Alarm - An alarm setpoint has been reached or exceeded.
The compressor will continue to run if running.
Manual - The device is being controlled from direct com-
mands or keys at the local controller.
Auto (Automatic) - The device is being controlled from
setpoints at the local controller.
Remote - The device is being controlled by a remote con-
troller.
GRAPHIC SCREEN
“OPERATING STATUS” SCREEN
Also called the “Home” screen. The most important infor-
mation about the compressor unit and the subsystems op-
eration is displayed here. This screen is shown when power
is first turned on and when a key is pressed after the screen
saver has turned off the backlight. The “Operating Status”
screen is continuously updated and provides a variety of
information in regard to the current condition and perfor-
mance of the compressor unit and subsystem.
The following information is shown on the left side of this
display:
COMPRESSOR DATA BOX:
Shows the present operating status of the compressor and
from what source it has been initiated:
Status - One of the following messages is shown:
Off
Starting
Running
Stopping 00:00
Mode - One of the following messages is shown:
Manual - A compressor manual start or stop
command was sent.
Automatic - The compressor auto command
was sent. The compressor starting and stop-
ping is being controlled from automatic cy-
cling control setpoints at the panel. The auto-
matic cycling control setpoints of the active
capacity control are used.
Remote - The compressor remote command
was sent. The compressor starting and stop-
ping is through the serial com2 channel.
Note: If there is a shutdown in response to a
safety setting, a compressor in “Remote” or
“Automatic” mode is placed into “Manual” mode
requiring operator intervention.
Recycle Delay - This message shows the remaining
time in minutes for Recycle Delay. If the compressor
has started and shut down within the recycle time de-

Table of Contents

Other manuals for Frick QUANTUM

Related product manuals