FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 75
after 12 seconds from the compressor stop command the
Motor Current reading is above the “Low Motor Amps Shut-
down” setpoint. While this condition is present, the Oil Pump
(if available) is on and Liquid Injection (if available) is al-
lowed on and the Slide Valve is unloaded to 0% to safe-
guard the compressor.
Compressor Unable to Unload - Alarm - While stopping
the compressor or the compressor is off, the Slide Valve
position has not unloaded below the “Highest Slide Valve
Position to allow starting the compressor” setpoint.
DBS Alarm - The RAM DBS Motor Starter is responding
that it has an alarm condition.
DBS Trip - The RAM DBS Motor Starter is responding that it
has a shutdown condition.
Digital Board 1 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Digital Board 1.
Digital Board 2 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Digital Board 2.
Digital Board 3 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Digital Board 3.
Digital Board 4 Comm. Fail - Shutdown - It has been de-
tected that the program is no longer able to communicate to
Digital Board 4.
Discharge Pressure Sensor Fault - This shutdown mes-
sage is issued if the discharge pressure reading was out of
range for its sensor.
Discharge Temperature Sensor Fault - This shutdown
message is issued if the Discharge Temperature reading
was out of range for its sensor.
False Start Failure - Aux. - This shutdown message is issued if
while the compressor is off the compressor auxiliary is ener-
gized. While this condition is present, the Oil Pump (if available)
is on and Liquid Injection (if available) is allowed on and the
Slide Valve is unloaded to 0% to safeguard the compressor.
False Start Failure - Motor Amps - This shutdown mes-
sage is issued if while the compressor is off, the Motor Current
reading is above the “Low Motor Amps Shutdown” setpoint. While
this condition is present, the Oil Pump (if available) is on and Liquid
Injection (if available) is allowed on and the Slide Valve is unloaded
to 0% to safeguard the compressor.
High Auxiliary Analog #1 Alarm - The Auxiliary Analog #1
value was greater than or equal to the high Auxiliary Ana-
log #1 alarm setpoint for its time delay.
High Auxiliary Analog #1 Shutdown - The Auxiliary Ana-
log #1 value was greater than or equal to the high Auxiliary
Analog #1 shutdown setpoint for its time delay.
High Auxiliary Analog #2 Alarm - The Auxiliary Analog #2
value was greater than or equal to the high Auxiliary Ana-
log #2 alarm setpoint for its time delay.
High Auxiliary Analog #2 Shutdown - The Auxiliary Ana-
log #2 value was greater than or equal to the high Auxiliary
Analog #2 shutdown setpoint for its time delay.
High Auxiliary Analog #3 Alarm - The Auxiliary Analog #3
value was greater than or equal to the high Auxiliary Ana-
log #3 alarm setpoint for its time delay.
High Auxiliary Analog #3 Shutdown - The Auxiliary Ana-
log #3 value was greater than or equal to the high Auxiliary
Analog #3 shutdown setpoint for its time delay.
High Auxiliary Analog #4 Alarm - The Auxiliary Analog #4
value was greater than or equal to the high Auxiliary Ana-
log #4 alarm setpoint for its time delay.
High Auxiliary Analog #4 Shutdown - The Auxiliary Ana-
log #4 value was greater than or equal to the high Auxiliary
Analog #4 shutdown setpoint for its time delay.
High Auxiliary Analog #5 Alarm - The Auxiliary Analog #5
value was greater than or equal to the high Auxiliary Ana-
log #5 alarm setpoint for its time delay.
High Auxiliary Analog #5 Shutdown - The Auxiliary Ana-
log #5 value was greater than or equal to the high Auxiliary
Analog #5 shutdown setpoint for its time delay.
High Auxiliary Analog #6 Alarm - The Auxiliary Analog #6
value was greater than or equal to the high Auxiliary Ana-
log #6 alarm setpoint for its time delay.
High Auxiliary Analog #6 Shutdown - The Auxiliary Ana-
log #6 value was greater than or equal to the high Auxiliary
Analog #6 shutdown setpoint for its time delay.
High Auxiliary Analog #7 Alarm - The Auxiliary Analog #7
value was greater than or equal to the high Auxiliary Ana-
log #7 alarm setpoint for its time delay.
High Auxiliary Analog #7 Shutdown - The Auxiliary Ana-
log #7 value was greater than or equal to the high Auxiliary
Analog #7 shutdown setpoint for its time delay.
High Auxiliary Analog #8 Alarm - The Auxiliary Analog #8
value was greater than or equal to the high Auxiliary Ana-
log #8 alarm setpoint for its time delay.
High Auxiliary Analog #8 Shutdown - The Auxiliary Ana-
log #8 value was greater than or equal to the high Auxiliary
Analog #8 shutdown setpoint for its time delay.
High Auxiliary Analog #9 Alarm - The Auxiliary Analog #9
value was greater than or equal to the high Auxiliary Ana-
log #9 alarm setpoint for its time delay.
High Auxiliary Analog #9 Shutdown - The Auxiliary Ana-
log #9 value was greater than or equal to the high Auxiliary
Analog #9 shutdown setpoint for its time delay.
High Discharge Temperature Alarm - The Discharge Tem-
perature was greater than or equal to the High Discharge
Temperature Alarm setpoint for its time delay.
High Discharge Temperature Shutdown - The Discharge
Temperature was greater than or equal to the High Dis-
charge Temperature Shutdown setpoint for its time delay.
High Discharge Pressure Alarm - The Discharge Pres-
sure was greater than or equal to the active High Discharge
Pressure Alarm setpoint for its time delay.
High Discharge Pressure Shutdown - The Discharge Pres-
sure was greater than or equal to the active High Discharge
Pressure Shutdown setpoint for its time delay.