FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 76
High Economizer Alarm - The Auxiliary Analog #10 value
was greater than or equal to the high Auxiliary Analog #10
alarm setpoint for its time delay.
High Economizer Shutdown - The Auxiliary Analog #10
value was greater than or equal to the high Auxiliary Ana-
log #10 shutdown setpoint for its time delay.
High Entering Process Temperature Alarm - The Enter-
ing Process Temperature was greater than or equal to the
“High Entering Process Temperature Alarm” setpoint for its
time delay.
High Entering Process Temperature Shutdown - The En-
tering Process Temperature was greater than or equal to
the “High Entering Process Temperature Shutdown” set-
point for its time delay.
High Liquid Level Shutdown - The corresponding input
module was de-energized.
High Motor Current Alarm - The Motor Amps was greater
than or equal to the High Motor Amps Alarm setpoint for its
time delay.
High Motor Current Shutdown - The Motor Amps was
greater than or equal to the High Motor Amps Shutdown
setpoint for its time delay.
High Oil Filter Pressure Alarm - The Oil Filter Pressure
was greater than or equal to the “High Filter Pressure Alarm”
setpoint for its time delay.
High Oil Filter Pressure Shutdown - The Oil Filter Pressure
was greater than or equal to the “High Filter Pressure Shut-
down” setpoint for its time delay.
High Oil Temperature Alarm - The Oil Temperature was
greater than or equal to the “High Oil Temperature Alarm”
setpoint for its time delay.
High Oil Temperature Shutdown - The Oil Temperature was
greater than or equal to the “High Oil Temperature Shut-
down” setpoint for its time delay.
Hi Suction Pressure Alarm - The Suction Pressure was
greater than or equal to the active High Suction Pressure
Alarm setpoint for its time delay.
Hi Suction Pressure Shutdown - The Suction Pressure
was greater than or equal to the active High Suction Pres-
sure Shutdown setpoint for its time delay.
Insufficient Main Oil Pressure Shutdown - The Slide Valve is
greater than 50% and the Oil Pressure (PSIA) is less than or
equal to the Suction Pressure (PSIA) multiplied by 1.5 and
then added to 15.0.
Low Auxiliary Analog #1 Alarm - The Auxiliary Analog #1
value was less than or equal to the low Auxiliary Analog #1
alarm setpoint for its time delay.
Low Auxiliary Analog #1 Shutdown - The Auxiliary Analog
#1 value was less than or equal to the low Auxiliary Analog
#1 shutdown setpoint for its time delay.
Low Auxiliary Analog #2 Alarm - The Auxiliary Analog #2
value was less than or equal to the low Auxiliary Analog #2
alarm setpoint for its time delay.
Low Auxiliary Analog #2 Shutdown - The Auxiliary Analog
#2 value was less than or equal to the low Auxiliary Analog
#2 shutdown setpoint for its time delay.
Low Auxiliary Analog #3 Alarm - The Auxiliary Analog #3
value was less than or equal to the low Auxiliary Analog #1
alarm setpoint for its time delay.
Low Auxiliary Analog #3 Shutdown - The Auxiliary Analog
#3 value was less than or equal to the low Auxiliary Analog
#3 shutdown setpoint for its time delay.
Low Auxiliary Analog #4 Alarm - The Auxiliary Analog #4
value was less than or equal to the low Auxiliary Analog #4
alarm setpoint for its time delay.
Low Auxiliary Analog #4 Shutdown - The Auxiliary Analog
#4 value was less than or equal to the low Auxiliary Analog
#4 shutdown setpoint for its time delay.
Low Auxiliary Analog #5 Alarm - The Auxiliary Analog #5
value was less than or equal to the low Auxiliary Analog #5
alarm setpoint for its time delay.
Low Auxiliary Analog #5 Shutdown - The Auxiliary Analog
#5 value was less than or equal to the low Auxiliary Analog
#5 shutdown setpoint for its time delay.
Low Auxiliary Analog #6 Alarm - The Auxiliary Analog #6
value was less than or equal to the low Auxiliary Analog #6
alarm setpoint for its time delay.
Low Auxiliary Analog #6 Shutdown - The Auxiliary Analog
#6 value was less than or equal to the low Auxiliary Analog
#6 shutdown setpoint for its time delay.
Low Auxiliary Analog #7 Alarm - The Auxiliary Analog #7
value was less than or equal to the low Auxiliary Analog #7
alarm setpoint for its time delay.
Low Auxiliary Analog #7 Shutdown - The Auxiliary Analog
#7 value was less than or equal to the low Auxiliary Analog
#7 shutdown setpoint for its time delay.
Low Auxiliary Analog #8 Alarm - The Auxiliary Analog #8
value was less than or equal to the low Auxiliary Analog #8
alarm setpoint for its time delay.
Low Auxiliary Analog #8 Shutdown - The Auxiliary Analog
#8 value was less than or equal to the low Auxiliary Analog
#8 shutdown setpoint for its time delay.
Low Auxiliary Analog #9 Alarm - The Auxiliary Analog #9
value was less than or equal to the low Auxiliary Analog #9
alarm setpoint for its time delay.
Low Auxiliary Analog #9 Shutdown - The Auxiliary Analog
#9 value was less than or equal to the low Auxiliary Analog
#9 shutdown setpoint for its time delay.
Low Economizer Alarm - The Auxiliary Analog #10 value
was less than or equal to the low Auxiliary Analog #10
alarm setpoint for its time delay.
Low Economizer Shutdown - The Auxiliary Analog #10
value was less than or equal to the low Auxiliary Analog
#10 shutdown setpoint for its time delay.
Low Entering Process Temperature Alarm - The Enter-
ing Process Temperature was less than or equal to the “Low En-
tering Process Temperature Alarm” setpoint for its time delay.