FRICK QUANTUM CONTROL PANEL
OPERATION
S90-010 O
Page 66
Suction Pressure Pull Down - This option provides for
a slow lowering of the Suction Pressure when in Suc-
tion Pressure Capacity Control. Slowly “walking” the
pressure down prevents rapid drops in system pres-
sure that causes violent boiling of refrigerant in the
system.
[Enable] - This key is provided if the control is
disabled.
[Disable] - This key is provided if the control is
enabled.
Hot Gas Bypass/SV Setpoint - This option is available
if it applies to the compressor model (Reference “Com-
pressor Model Differences”). This feature is provided to
turn on up to three digital outputs based on an entered
Slide Valve position setpoint. For further setup see the
“Slide Valve Setpoints” screen. A toggle key is provided
that changes between the following selections:
[Hot Gas Enable] - This key is provided if the con-
trol is disabled.
[Hot Gas Disable] - This key is provided if the
control is enabled.
Auxiliaries 3-8 - This provides for selecting additional
(more than 2) auxiliary digital input modules to be used
as an alarm or a shutdown when the auxiliary input is
de-energized. For further setup see the “Auxiliaries 3-8
Setup” display. A toggle key is provided that changes
between the following selections:
[Auxiliary Inputs Enable] - This key is provided if
feature is disabled.
[Auxiliary Inputs Disable] - This key is provided if
feature is enabled.
Pumpdown/DX Circuit - This option is available if it
applies to the compressor model (Reference “Compres-
sor Model Differences”). This provides for setup of the
DX (direct expansion) circuits (DX Circuit #1 and DX
Circuit #2). Settings will determine when these digital
outputs are turned on and off. For further setup see the
“Pumpdown/DX Circuit” screen. A toggle key is pro-
vided that changes between the following selections:
[Enable] - This key is provided if feature is disabled.
[Disable] - This key is provided if feature is en-
abled.
Kilowatt Monitor Calibration and Setup - This provides
for using the kW Monitoring analog channel 16. If Kilo-
watt monitoring is enabled, the current value of the kW
Monitoring analog input is displayed on the “Operating
Status” screen. For further setup see the “Kilowatt Moni-
tor Calibration” screen. A toggle key is provided that
changes between the following selections:
[Kilowatt Monitor Enable] - This key is provided if
feature is disabled.
[Kilowatt Monitor Disable] - This key is provided if
feature is enabled.
Auxiliary Analog Temperature and Pressures - This
provides for using one or up to ten analog input auxil-
iaries to monitor either temperature or pressure read-
ings. For further setup see the “Auxiliary Analog Tem-
peratures & Pressures” screen and the “Calibrate Aux-
iliary Analog” screen. A toggle key is provided that
changes between the following selections:
[Analog Auxiliaries Enable] - This key is provided
if feature is disabled.
[Analog Auxiliaries Disable] - This key is provided
if feature is enabled.
Entering Process Temperature - This provides for us-
ing the Entering Process Temperature analog channel
4. If this is enabled, the current value of the Entering
Process Temperature analog input is displayed on the
“Operating Status” screen. For further setup see the
“Temperature Calibration” screen and the “Entering
Process Safeties” screen. A toggle key is provided that
changes between the following selections:
[Entering Process Enable] - This key is provided
if feature is disabled.
[Entering Process Disable] - This key is provided
if feature is enabled.
Slide Valve Position Control - This option is available
if it applies to the compressor model (Reference “Com-
pressor Model Differences”). This provides for using
the Remote Slide Valve Position analog channel 13.
The remote (4-20 ma) input signal to this channel can
be used to control the Slide Valve. For further setup see
the “Calibrate Slide Valve Position” screen and the [Re-
mote Slide Valve] command key from the Slide Valve
mode screen command keys on the “Operating Status”
screen. A toggle key is provided that changes between
the following selections:
[Slide Valve Position Enable] - This key is pro-
vided if feature is disabled.
[Slide Valve Position Disable] - This key is pro-
vided if feature is enabled.
Remote Control Setpoint - This provides for using the
Remote Control Setpoint analog input (channel 12)
and the Remote Control Setpoint analog output (chan-
nel 4) for Capacity Control of compressors. For further
setup see the “Calibrate Remote Control Setpoint”
screen and the [Remote Setpoint] command key from
the Slide Valve mode screen command keys on the
“Operating Status” screen. A toggle key is provided
that changes between the following selections:
[Remote Setpoint Enable] - This key is provided if
this feature is disabled.
[Remote Setpoint Disable] - This key is provided
if this feature is enabled.
Permissive Start - The input used for this feature is
Module 17 on the Digital I/O Board 2.
[Always] - This input must be energized to start
the compressor. And if the compressor is running
and this input is deenergized, the compressor is
stopped.
[Starting] - This input needs to be energized only
to start the compressor.
[Disable] - This key is provided to disable this
feature.