signals may be attenuated or amplified by the inverter. The settings below can be
used to counteract this if necessary.
Parameter Range of val-
ues
Description
"Reduction of
Influence"
Off The function is deactivated.
On The function is activated.
"Frequency of
Ripple Control
Signal"
100 ‑ 3000 Hz The frequency specified by the energy
company must be entered here.
"Grid Induct-
ance"
0.00001 ‑ 0.00
5 H
The value measured at the feed-in point
must be entered here.
"Measure against RCD false triggers"
(when using a 30 mA residual current circuit breaker)
NOTE!
National regulations, the grid operator's specifications or other factors may re-
quire a residual current circuit breaker in the AC connection lead.
For this situation, a type A residual-current circuit breaker is generally adequate.
Nevertheless, false alarms can be triggered for the type A residual current circuit
breaker in individual cases and depending on local conditions. For this reason, in
accordance with national legislation, Fronius recommends that a residual current
circuit breaker with a tripping current of at least 100 mA suitable for frequency
converters be used.
Parameter Range of val-
ues
Description
"Switch-Off be-
fore 30mA RCD
Trip" (only for
Primo GEN24)
0 No measures to prevent false tripping.
1 The inverter switches off at 15 mA before
the residual current circuit breaker trips.
"Leakage Cur-
rent Factor"
(only for Symo
GEN24)
0 ‑ 0.25
(default: 0.16)
Reducing the setting value reduces the
leakage current and raises the intermedi-
ate circuit voltage, which slightly reduces
the efficiency. Setting value 0.16 enables
optimum efficiency.
"Iso Warning"
Parameter Range of val-
ues
Description
"Iso Warning" Off The isolation warning is deactivated.
On The isolation warning is activated.
A warning is issued in the event of an isola-
tion fault.
107
EN