Adjustable range of continuous resid-
ual current monitoring
9)
30 - 300 mA
Cyclic repetition of the insulation res-
istance test (on delivery)
24h
Adjustable range for the cyclic repeti-
tion of the insulation resistance test
-
DC input data battery
8)
Max. voltage 531 V / 700 V *
* only with suitable disconnection
device between inverter and battery in
the event of a fault
Min. voltage 160 V
Max. current 22 A
Max. output 6000 W
DC inputs
1
AC input/output data
Rated power (P
nom
) 6000 W
Max. output power 6000 W
Rated apparent power 6000 W
Nominal mains voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Min. mains voltage
154 V
1)
Max. mains voltage
280 V
1)
Max. output current
16.4 A
Nominal output current (at 230 V) 8.7 A
Current (inrush)
6)
9.9 A / 4 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion < 3.5%
Power factor cos phi
2)
0-1 (adjustable)
0.7-1 (recommended)
Max. permitted mains impedance Z
max
at PCC
4)
None
Maximum output fault current / dura-
tion
80.7 A / 10 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal mains voltage
1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
161