EasyManua.ls Logo

Fuji Electric Frenic-Mini - Page 111

Fuji Electric Frenic-Mini
366 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.2 Selecting Wires and Crimp Terminals
6-11
Chap. 6 SELECTING PERIPHERAL EQUIPMENT
Table 6.3 Cont. (HP, AWG ratings) (for DC reactor, braking resistor, control circuit, and inverter grounding)
Recommended wire size (AWG) at 40°C (104°F) or below
DC reactor
[P1, P(+)]
Braking resistor
[P(+), DB]
Control circuit
Inverter
grounding z[G]
Allowable
temp.*1
Allowable
temp.*1
Allowable
temp.*1
Allowable
temp.*1
Power
supply
voltage
Applicable
motor
rating
(HP)
Inverter type
140°F167°F194°F
Current
(A)
140°F167°F194°F
Current
(A)
140°F 167°F 194°F 140°F 167°F194°F
1/8 FRN0001C2S-2 0.7
1/4 FRN0002C2S-2 1.1
- - - -
1/2 FRN0004C2S-2 2.0 1.2
1 FRN0006C2S-2 3.7 1.6
2 FRN0010C2S-2 7.0 3.6
3 FRN0012C2S-2 10.2 3.5
5 FRN0020C2S-2
14
17.2 4.1
14 14 14
7.5 FRN0025C2S-2 12
14 14
25.9 6.4 12 12 12
10 FRN0033C2S-2 10 12 12 35.3 6.1
15 FRN0047C2S-2 10 10 51.7 9.1
10 10 10
Three-
phase
230 V
20 FRN0060C2S-2
6
6 8 70.6
14 14 14
11
20 20 20
8 8 8
1/2 FRN0002C2-4 1.0 0.8
1 FRN0004C2-4 1.9 1.1
2 FRN0005C2-4 3.6 1.8
3 FRN0007C2-4 5.3 1.8
5 FRN0011C2-4 9.0 2.1
7.5 FRN0013C2-4 13.0 3.2
14 14 14
10 FRN0018C2-4
14
17.7 3.1
15 FRN0024C2-4 12
14 14
25.9 4.5
Three-
phase
460 V
20 FRN0030C2-4 10 12 12 35.3
14 14 14
5.7
20 20 20
12 12 12
1/8 FRN0001C2-7 1.1
1/4 FRN0002C2-7 2.0
- - - -
1/2 FRN0004C2-7 3.5 0.82
1 FRN0006C2-7 6.4 1.4
2 FRN0010C2-7 11.7 1.4
Single-
phase
230 V
3 FRN0012C2-7
14 14 14
17.5
14 14 14
1.7
20 20 20 14 14 14
1/8 FRN0001C2S-6U
1/4 FRN0002C2S-6U
- - - -
1/2 FRN0003C2S-6U 0.82
Single-
phase
115 V
1 FRN0005C2S-6U
- - - -
14 14 14
1.4
20 20 20 14 14 14
*1 Assuming the use of bare wiring (without rack or duct): 600 V class of vinyl-insulated IV wires for 60°C (140°F), 600 V
class of polyethylene-insulated HIV wires for 75°C (167°F), and 600 V class of polyethylene-insulated cross-link wires for
90°C (194°F).
Notes: 1) A box () in the above table replaces A, C, E, or U depending on shipping destination.
2) A box (
) in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the
enclosure.
3) Values in parentheses ( ) in the above table denote wire sizes for the European version.
If environmental requirements such as power supply voltage and ambient temperature differ
from those listed above, select wires suitable for your system by referring to Table 6.1 and
Appendices, App. F "Allowable Current of Insulated Wires."

Table of Contents

Other manuals for Fuji Electric Frenic-Mini

Related product manuals