8.3 Common Specifications
8-7
Chap. 8 SPECIFICATIONS
8.3 Common Specifications
Item Explanation
Maximum frequency 25.0 to 400.0 Hz variable
Base frequency 25.0 to 400.0 Hz variable
Starting frequency 0.1 to 60.0 Hz variable
Setting range
Carrier frequency 0.75 to 16 kHz variable
Note: To protect the inverter, when the carrier frequency is 6 kHz or more, the
carrier frequency automatically lowers depending upon the ambient
temperature or output current states. (The automatic lowering function can be
disabled.) *1
Output frequency accuracy
(Stability)
Analog setting: ±2% of max freq. (at 25°C),
temperature drift: ±0.2% of max freq. (at 25±10°C)
Keypad setting: ±0.01% of max freq. (at 25°C),
temperature drift: ±0.01% of max freq. (at 25±10°C)
Output frequency
Frequency setting resolution
• Analog setting: 1/1000 of maximum frequency
Keypad setting: 0.01 Hz (99.99 Hz or less), 0.1 Hz (100.0 to 400.0 Hz)
Link setting: 1/20000 of maximum frequency or 0.01 Hz (fixed)
Control system Driving induction motor (IM)
V/f control, slip compensation, auto torque boost
Dynamic torque vector control, automatic energy saving control
Driving permanent magnet synchronous motor (PMSM) (without speed /
position sensor) *2
Speed control range: 10% or more of the base frequency
200 V
class series
Possible to set output voltage at base frequency and at
maximum output frequency (80 to 240 V).
• The AVR control *1 can be turned ON or OFF.
• Non-linear V/f *1 setting (2 points): Free voltage (0 to 240 V)
and frequency (0 to 400 Hz) can be set.
Voltage/frequency
characteristics
400 V
class series
Possible to set output voltage at base frequency and at
maximum output frequency (160 to 500 V).
• The AVR control *1 can be turned ON or OFF.
• Non-linear V/f *1 setting (2 points): Free voltage (0 to 500 V)
and frequency (0 to 400 Hz) can be set.
Torque boost *1 Auto torque boost (For constant torque load)
• Manual torque boost Torque boost value can be set between 0.0 and
20.0%.
Select application load with the function code. (For variable torque load or
constant torque load)
Starting torque *1 150% or more (Running at 3 Hz, with auto torque boost active)
Keypad: Start and stop with RUN and STOP keys
(standard keypad/optional remote keypad)
External signals (digital inputs): Run forward and stop command, Run reverse
and stop command, coast-to-stop command, etc.
Control
Start/stop operation
Link operation: Operation through RS-485 (built-in as standard)
*1 Available only for induction motor drive.
*2 Not supported by the first version.